Daikin Self-Contained Water Source Heat Pump Unit Ventilator
Model ARQ - Standard Range
Model ERQ - Extended Range
Model GRQ - Geothermal Range
R-410A Refrigerant, MicroTech II™ (“F” Vintage)
Before beginning installation, please read this publication in its entirety.
Develop a thorough understanding before starting the installation procedure.
This manual is to be used as a guide. Each installation is unique, so only general topics are covered.
The order in which topics are covered may not be those required for the actual installation.
C
Installation Manual IM 1083
Group: Unit Ventilator
Part Number: 106506250
Date: October 2013
IMPORTANT!
©2013 Daikin Applied • www.DaikinApplied.com • (800) 432-1342
Przeglądanie stron 0
1 2 3 4 5 6 ... 41 42

Podsumowanie treści

Strona 1 - IM 1083

Daikin Self-Contained Water Source Heat Pump Unit VentilatorModel ARQ - Standard RangeModel ERQ - Extended RangeModel GRQ - Geothermal RangeR-410A Re

Strona 2

Page 10 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Figure 13: Above Floor Level Outdoor Air Intake with Accessory Closed

Strona 3 - Table of Contents

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 11 of 42 Figure 15: 21⅞" (556mm) Deep Full Adapter Back Unit and Floor L

Strona 4

Page 12 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Figure 19: The 21⅞” (556mm) Deep Full Adapter Back Unit with Closed Re

Strona 5 - Lifting Unit

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 13 of 42 Personal injury hazard. Wear protective gloves to avoid possible cu

Strona 6

Page 14 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Notes:1. Horizontal blade wall louver shown. Vertical blade wall lou

Strona 7 - Shutter Installation

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 15 of 42 Figure 29: Typical VentiMatic™ Shutter Assembly InstallationLouverO

Strona 8

Page 16 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Unit Ventilator InstallationBefore setting the unit ventilator in posi

Strona 9 - Shutter Assembly

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 17 of 42 Reversing Condensate Drain EndModels ARQ, ERQ and GRQ condensate dra

Strona 10

Page 18 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Figure 35: Unit Mounting Holes LocationsUnit Mounting Holes187/8″67/8″

Strona 11 - Pitch Away From Unit

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 19 of 42 Operating Limits1 At ISO 13256-1 flow rate.2 Maximum and minimum v

Strona 13

Page 20 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083 A B C Standard Static Pressure 1¼" 5/8" 2¾" High

Strona 14

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 21 of 42 Bypass valves at the heat rejector and supplementary water heater sh

Strona 15

Page 22 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Water Coil ConnectionsHook up water piping in accordance with Figure 3

Strona 16 - Preparing to Move the Unit

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 23 of 42 System BalancingThe recommended method, and the one most commonly us

Strona 17 - To Clean the Drain Pan

Page 24 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 10834. Tenant Override Switch: Provides a momentary contact closure that

Strona 18

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 25 of 42 15. Outdoor Air Temperature Sensor (S3): The sensor is located in t

Strona 19 - Start-up

Page 26 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Figure 46: Local User Interface (LUI)MicroTech IITMFAN ONLYCOOLHEATAU

Strona 20 - Piping Considerations

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 27 of 42 MicroTech II Wiring Diagram – TypicalFigure 47: DX Cooling w/Electr

Strona 21 - CAUTION

Page 28 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Table 11: Model ARQ, ERQ, GRQ Electrical Data – Size 024Table 12: Mo

Strona 22 - For All Systems

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 29 of 42 Table 13: Model ARQ, ERQ, GRQ Electrical Data – Size 048Electrical

Strona 23 - System Balancing

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 3 of 42 Table of ContentsNomenclature...

Strona 24 - Making Control Connections

Page 30 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083MicroTech II™ Unit Electrical ConnectionsTo avoid electrical shock, pe

Strona 25

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 31 of 42 GNDCommBI-6BI-5BI-4896908A907A906A905AShield896908907906905P1 (12-pi

Strona 26 - Occupancy Modes (4)

Page 32 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083 Maximum sensor wire length for less than 1°F error Gauge Lengt

Strona 27

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 33 of 42 Field Wiring Remote Mounted Temperature SensorThe low voltage eld w

Strona 28 - Electrical Data

Page 34 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Figure 62: Surface Mounting Using Large BaseMountingThe MicroTech II™

Strona 29

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 35 of 42 Setup and Adjustments – Switching Setpoint DialsTo switch setpoint d

Strona 30 - Procedure

Page 36 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083ElectroMechanical Unit Wiring ConnectionsElectromechanical control con

Strona 31

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 37 of 42 End Panel DimensionsInstalling (Optional) End Panel27 7/8"(708m

Strona 32 - Temperature Sensor

Page 38 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Piping Stub-up Within CabinetUnit End CompartmentPiping Stub-up Within

Strona 33

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 39 of 42 Figure 74: Fan Shaft Bearing(s) Oil Cup Location(s)Room Air Fan Sha

Strona 34 - IMPORTANT

Page 4 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083E9 = Expanded Stand-Alone w/o TC w/CO2 EA = Expanded Stand-Alone Ma

Strona 35 - Repairs and Replacement

Page 40 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Complete Check, Test and Start ProcedureRenewable Media (Single-use an

Strona 36 - Connections

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 41 of 42 Troubleshooting The in and outs of R-410AR-410A is a non-ozone deple

Strona 37 - End Panel Dimensions

Air Water Safety Head Suction Compressor Super Temp (loops) Temp LockSymptomPressure Pressure Amp Draw Heat SubcoolingDifferential Diffe

Strona 38 - End Panel Assembly

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 5 of 42 Make sure lifting equipment can handle the weight of the unit safely.

Strona 39 - Filter(s)

Page 6 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Pre-Installation Considerations Before beginning installation, plea

Strona 40

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 7 of 42 Figure 5: Typical Unit Ventilator Installation and Louver Details (se

Strona 41 - WARNING

Page 8 of 42 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ IM 1083Pre-Installation Considerations Meeting IBC Seismic RequirementsDaikin

Strona 42

IM 1083 Self-Contained WSHP Unit Ventilator Models ARQ, ERQ, GRQ Page 9 of 42 Figure 9: Horizontal and Vertical Blade Louvers, Without Flanges With